![]() Danfoss mechanical pressure switch | ||
| Ambient temperature | -40-65DegC(80DegC for max 2 hours) | |
| Ambient temperature (PED approved units) | -25-65DegC(80DegC for max 2 hours) | |
| Media temperature | -50-100DegC | |
| Max. working pressure | LP:PS / MWP = 17bar | |
| HP:PS / MWP = 35bar | ||
| KP 6:PS / MWP = 46.5bar | ||
| Max. test pressure | LP:Pe = 20bar | |
| HP:Pe = 35bar | ||
| KP 6:Pe = 46.5bar | ||
| Contact load | Alternating current | AC1 = 16A, 400V |
| AC3 = 16A, 400V | ||
| AC15 = 10A, 400V | ||
| Direct current | DC13:12W, 220V control current | |
| Wire dimensions | solid/stranded | 0.75 - 2.5mm2 |
| flexible, without ferrules | 0.7 - 2.5mm2 | |
| flexible, with ferrules | 0.5 - 1.5mm2 | |
| Tightening torque | max.2 Nm | |
| Rated impulse voltage | 4kV | |
| Pollution degree | 3 | |
| Short circuit protection, fuse | 16A | |
| Insulation | 400V | |
| Enclosure | IP30/IP44/IP55 | |